Introduction and General Information
ADDvantage-32 PLUS ● AC to DC Power Converter
1-34
TABLE 1-1. ADDvantage-32 PLUS SPECIFICATIONS--Cont.
DESCRIPTION SPECIFICATION*
Chassis Ambient Temperature
- Enclosed (See outline drawing for minimum
enclosure size.)
- Open Chassis
0 to 40º C (32 to 104º F)
0 to 50º C (32 to 122º F) (50º C maximum
surrounding air temperature rating)
Storage Temperature*** -20 to 55º C (-4 to 131º F)
Relative Humidity 95% non-condensing
Operational Altitude 0 to 3,300 feet above sea level –
no derating required.
Above 3,300 feet –
derated linearly by 1% per 300 ft.
Worst Case Power Loss
Drive P/N Watts (approximate)
DC0010 150
DC0030 200
DC0056 260
DC0110 500
DC0180 725
DC0280 1000
DC0360 1150
DC0510 1400
DC054X 1500
DC055X 2050
DC085X 2300
DC155X-4 3900
DC155X-B 4500
DC250X 6100
DC300X-A 7900
DC300X-B 8300
Power loss follows the approximate curve
shown in Figure 1-17. Worst case power
loss (total) is at 100% speed, 100% load.
At other speeds and loads the percent loss
is greater, but the total loss is less.
25 50 75 100% SPEED
100
99
98
97
96
95
E
F
F
E
C
I
E
N
C
Y
100%LOAD
25%LOAD
EFFICLAN
Figure 1-17. Efficiency vs. Speed
* Additional Specifications are located in the supplemental drawing package.
*** A space heater may be necessary if condensation or excessive moisture is expected.