Core Software Operation
ADDvantage-32 PLUS ● AC to DC Power Converter
3-23
Calibrate the pulse train into a user value by using the following equation:
A***:SPEED IN 1=
[(INPUT FREQ) × (EDGE/PULSE) + (TACH 1 ZERO)] × (60) × (π) × (TACH 1 RDia)
(TACH 1 EPR) × TACH 1 GRat
EDGES/PULSE = 1 is used for one phase, one edge applications
2 is used for one phase, two edge applications
4 is used for two phase, two edge applications
For example, to calibrate the frequency input into feet per minute from the following
machine data:
2-phase, 240 PPR pulse generator mounted on the motor shaft
3.0 gear ratio from motor to roll
Roll diameter of 24 inches
1. Select the tach type required by setting Y***:TACH 1 TYPE=Q***:2
PHASE-S or Q***:TWO PHASE.
2. Set X***:TACH EPR = 960. Pulses per revolution of the pulse generator
times four edges per pulse.
3. Set X***:TACH GRat = 3.0 per the given machine data.
4. Set X***:TACH RDia = 2, which is the diameter of the roll in process
units (feet).
3.11 COUNTERS
X*** Parameters Y*** Parameters Analog Data Table
X***:COUNT 1 CAL Y***:CTR 1 RESET A***:FOOTAGE 1
X***:COUNT 2 CAL Y***:CTR 1 HOLD A***:FOOTAGE 2
Y***:CTR 2 RESET A***:DIF FOOTAGE
Y***:CTR 2 HOLD
Y***:DIF-CTR RST
Y***:DIF-CTR HLD
The frequency inputs correspond to an associated counter. The counter increases one unit
for every pulse edge detected. The increment value is determined as follows:
A***:FOOTAGE 1 = (1, 2 or 4 Edges/Pulse) (Pulses) X***:COUNT 1 CAL
Where: 1 - Is used when the frequency input is set up for 1 PHASE,