Maintenance and Troubleshooting
ADDvantage-32 PLUS AC to DC Power Converter
7-10
CONTACTOR (Y***:F-CLR ON M).
In addition to clearing the actual fault, the fault queue can also be cleared in one
of two ways:
1) The user may clear the fault FIFO by using the FAULT FIFO CLEAR
syntax in the FAULT menu.
2) The user may configure the drive to clear the fault fifo on the positive
transition of a bit in the digital table (Y***:F-FIFO CLR).
TYPES OF WARNINGS AND FAULTS
A. Hardcoded Faults and Warnings - Hardcoded faults are not user-
definable. Some hardcoded events are only valid when the motor
contactor is picked up. See Table 7-3 for a list of faults, warnings,
and motor contactor status. See Table 7-4 for fault messages and
corrective action.
B. User Defined Faults/Warnings - There are eight possible user
defined fault messages which may be configured to any digital
data point. The defined faults are Y***:USR FAULT 1 through
Y***:USR FAULT 8. The label of the digital data point the user
fault is configured for is shown in the fault FIFO.