Core Software Operation
ADDvantage-32 PLUS ● AC to DC Power Converter
3-8
D:RUNX picked up on a run, jog, or thread command is requested. It stays in
until the D:SPD MIN PT goes high or there is a fault or ESTOP. If you want the
contactor to open immediately after run removal, configure D:SPD MIN PT to
D:ONE BIT or else set it equal to D:AT ZERO SPD.
RUNG 9 Delay to hold in the motor contactor and SCR enable while armature current
magnitude is greater than a small minimum value. It allows a delay of up to half a
second.
RUNG 10 This sets the seal-in bit to keep the motor contactor in and the SCR's enabled
while the magnitude of armature current is greater than a small minimum value
or a half second after the contactor is commanded open.
Figure 3-1. ADDvantage-32 PLUS Logic Diagram (sheet 4 of 14)