Introduction and General Information
ADDvantage-32 PLUS ● AC to DC Power Converter
1-30
1.5 SPECIFICATIONS
Please note that some of the following specifications are not pertinent to all models.
TABLE 1-1. ADDvantage-32 PLUS SPECIFICATIONS
DESCRIPTION SPECIFICATION*
Input Voltage to Transformer 3-Phase primary windings to standard voltages
(Phase rotation insensitive)
Transformer Output to Drive** 3-Phase, 230 or 460 VAC (nominal), except
550 ADC Drive only - 230, 460, or 575 VAC
(nominal)
Maximum Currents
Drive HP Armature Input Field
P/N 240/500/700 VDC Output Current Output
DC0010 2/5 10 Amps DC 11 Amps AC 3 Amps DC
DC0030 7.5/15 30 Amps DC 28 Amps AC 3 Amps DC
DC0056 15/30 56 Amps DC 49 Amps AC 6 Amps DC
DC0110 30/60 110 Amps DC 95 Amps AC 6 Amps DC
DC0180 50/100 180 Amps DC 155 Amps AC 12 Amps DC
DC0280 75/150 280 Amps DC 240 Amps AC 12 Amps DC
♦
DC0360 100/200 360 Amps DC 310 Amps AC 12 Amps DC
♦
DC0510 150/300 510 Amps DC♦♦ 416 Amps AC 12 Amps DC
♦
DC0540 150/300 540 Amps DC 440 Amps AC 12 Amps DC
DC0541 150/300 540 Amps DC 440 Amps AC 24 Amps DC
DC0542 150/300 540 Amps DC 440 Amps AC 48 Amps DC
DC0550 150/300/400 550 Amps DC 459 Amps AC 12 Amps DC
DC0551 150/300/400 550 Amps DC 470 Amps AC 24 Amps DC
DC0552 150/300/400 550 Amps DC 488 Amps AC 48 Amps DC
DC0850 250/500 850 Amps DC 700 Amps AC 12 Amps DC
DC0851 250/500 850 Amps DC 700 Amps AC 24 Amps DC
DC0852 250/500 850 Amps DC 700 Amps AC 48 Amps DC
DC1550 500/1000/1250 1550 Amps DC 1265 Amps AC 12 Amps DC
DC1551 500/1000/1250 1550 Amps DC 1265 Amps AC 24 Amps DC
DC1552 500/1000/1250 1550 Amps DC 1265 Amps AC 48 Amps DC
DC3000 900/1800/2500 3000 Amps DC 2460 Amps AC 12 Amps DC
DC3001 900/1800/2500 3000 Amps DC 2470 Amps AC 24 Amps DC
DC3002 900/1800/2500 3000 Amps DC 2490 Amps AC 48 Amps DC
♦ Additional Specifications are located in the supplemental drawing package.
♦♦ An isolation transformer or line reactor is required when applying each ADD-32 PLUS drive to a power distribution system.
A total impedance from the power distribution source to the drive input in the range of 3% to 6% is required. Total KVA
rating of transformer should not exceed 3 times the drive rating. If a drive isolation transformer is supplying power to multiple
drives, then each drive must have a line reactor. If a combination of isolation transformer and line reactor is used, the reactor
should contribute the majority of the line impedance (better than 2:1 ratio). Provided that each ADD-32 PLUS has the proper
source impedance, any number of drives or frame sizes can be connected to a common power source. Connection of any
power converter to a transformer with primary rating of 2300 VAC or more may require additional input line conditioning at
the power converter to prevent damage to electrical components. Contact Avtron Industrial Automation, Inc., for assistance
when this is required.
♦ A 24 amp field option is available on drives with a 12 amp field.
♦♦ Consult factory for overload rating.