Control Block Description
ADDvantage-32 PLUS
4-95
FIGURE 4-61B
The maximum rate of change allowed by the RMP2 ROC filter block depends upon time.
This time is measured from the beginning of a ramp input to the present time instant. The
maximum rate of change of the output of this filter is time dependent of the form:
Rate = S × T
Equation 4-61.1
where S is the analog value RND (units/Sec.
2
), and T (Sec.) is the point in time since the
start of the ramp input. The maximum rate of change of the filter output will not exceed
that of the input over a long enough time interval.
As an example, note on Figure 4-61B that the plot starts at time t = 0 Sec. The rate of
change at the input of the filter block is a constant 20 FPM/S. The filter limits the rate of
change block to 5FPM/Sec
2
thus: