Digital Acoustics ESBx-110 Especificaciones Pagina 40

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 466
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 39
Introduction and General Information
ADDvantage-32 PLUS AC to DC Power Converter
1-33
TABLE 1-1. ADDvantage-32 PLUS SPECIFICATIONS--Cont.
DESCRIPTION SPECIFICATION*
Diagnostics 40 fault messages w/corrective action
11 front panel LED annunciators
16 event fault memory
Signal Analyzer
Sampling Rate -
360 Samples/Second Max.,
27.8 Seconds/Sample Min.
Recording Duration -
61.7 hours Max.,
22.22 seconds Min.
RS485 Serial Link Optically-isolated Self powered.
120V common mode noise rejection
Pulse Generator Inputs: 2-Phase 3-30V peak-to-peak,
540 ohm impedance,
Optically isolated,
120V common mode rejection,
0-20,200 Hz frequency range,
50% +20% duty cycle
Buffered Pulse Generator Outputs: 2-Phase 5V @ 50mA,
0-25 KHz frequency range
Auxiliary Power Supplies Digital I/O Supply
Voltage Output = 24 VDC Nom., 26 VDC Max.
Current Output = 80 mADC Max.
Auxiliary AC Supply
Voltage Output = 115 VAC Nom.
Power Output =
50 VA Max. (units 56A and under)
100 VA Max. (units 110A and above)
Safety Interlock Supply
Voltage Output = 24 VDC Nom., 26 VDC Max.
Current Output = 50 mADC Max.
Pulse Generator Supply
Voltage Output = 12 VDC Nom., 13.2 VDC Max.
Current Output = 300 mA Max. (Short circuit proof)
Pot Supplies
Voltage Output = ±10 VDC Max.
Current Output = 5 mA Max.
* Additional Specifications are located in the supplemental drawing package.
Consult Avtron regarding UNIPULSER
TM
information for additional duty cycle applications.
Vista de pagina 39