Maintenance and Troubleshooting
ADDvantage-32 PLUS ● AC to DC Power Converter
7-14
FAULT MESSAGE PROBLEM SOLUTION
IARM VOFFST The drive firmware has
detected that the zero offset
of the armature current
feedback exceeded allowable
limits.
a. Replace microprocessor board
INST OVR CU Instantaneous Overcurrent-
Armature Current above
300%.
a. Retune unstable current loop.
b. Check for shorted motor armature.
c. Check for stable line voltage.
d. Replace bridge interface board.
e. Replace microprocessor board.
f. Replace base.
L-FREQ HIGH Line frequency above 65 Hz. a. Check plant power frequency.
b. Replace power supply board.
c. Replace microprocessor board.
L-FREQ LOW Line frequency below 43 Hz. a. Check plant power frequency.
b. Replace bridge interface board.
c. Replace microprocessor board.
LINE VOLTAG Low line voltage. Measure incoming voltage.
MOTOR (II) T Motor overtemperature due
to armature current above
110% for too long.
a. Undersized motor.
b. Parameter X001: MOTOR IARM
scaled wrong.
c. Parameter X002: MOTOR IFLD scaled
wrong.
d. Check bearings.
e. Check gearbox oil.
f. Replace bridge interface board.
g. Replace micro board.
MOTOR STALL Motor failed to move with
armature current.
a. Check setup of stall parameters.
b. Check for mechanical binding.
c. Check for correct armature and field
current scaling.
d. Check for correct speed feedback.
e. Replace motor.
MOTOR TEMP Motor Thermal Overload-
Armature Current above
100% for more than rated
time.
a. Enable P***:BYPASS I2R to auto
phase back current limits.
b. Check for proper field current.
c. Check for a mechanical problem
causing excess currents.
d. Check for proper current limit settings.