6.3 STORAGE AND INSTALLATION SPECIFICATIONS
If the ADD-32 PLUS is to be stored for an extended period of time prior to its
installation, the storage temperature should not fall below -20ºC and noncondensing
humidity should be no more than 95%. Installation conditions require an ambient
temperature of 0-40ºC when enclosed. Refer to the outline drawing provided in the
drawing package for enclosure size and cooling specifications. No derating is needed at
altitudes between 0-3,300 feet above sea level.
6.4 MOUNTING SPECIFICATIONS
All ADDvantage-32 PLUS models should be mounted vertically against a flat panel to
allow necessary cooling.
6.5 LOCATION
The equipment should be located where the operating ambient temperature does not
exceed 50ºC within an enclosure and where excessive shock and vibration are not
transmitted to the units. The equipment should be isolated from or protected against such
adverse environmental conditions as oil or water spray, and corrosive or conductive air
contaminants. Ideally, the equipment should be installed in an air-conditioned control
room. Refer to appropriate outline drawing for specific enclosure and ambient
temperature restrictions.
Location of Other Equipment
The ADD-32 PLUS Power Converter should be installed with sufficient distance from
other equipment so that the door may be opened during installation, maintenance, and
servicing without interfering with other equipment.
6.6 REMOTABLE KEYPAD
All ADDvantage-32 PLUS models come with a remotable keypad, which is supplied
installed on the drive. Refer to Remote Keypad Kit B39402 instructions for details on
how to remotely mount the keypad.