Preparation for Use
ADDvantage-32 PLUS ● AC to DC Power Converter
6-8
attached for each of the connection points. Refer to Table 6-3 for recommended wire
sizes.
Motor field output connections are made to terminals + and - of terminal block TB1
located at the bottom of the drive base assembly. No terminal lugs are required. Use
#12 AWG to #4 AWG wire. Strip insulation 0.59" from end of wire.
NOTE
Refer to appropriate outline drawing to determine voltage and
current ratings.
Optional auxiliary field excitation transformer connections are made directly to TB1
terminals 3, 4, 5 and 6. Use #12 AWG to #4 AWG wire. Strip insulation 0.39" from end
of wire.
Auxiliary control power connections are made directly to TB1 terminals 7 and 8. Use
#22 AWG to #12 AWG wire. Strip insulation 0.47" from end of wire.
M-Contactor auxiliary contact connections are made to TB1 terminals 14, 15, and 16.
These are rated to interrupt at a maximum of 5A, 300 V. Use #22 AWG to #14 AWG
wire. Strip insulation 0.39" from end of wire.
Additional control connections such as E-STOP, E-STOP RESET, and DOK OUT are
made to the quick connect plug connector at TB1 terminals 11, 12, 13, and 17, 18, 19,
and 20. Use #22 AWG to #14 AWG wire. Strip insulation 0.27" from end of wire.
System interconnections such as digital and analog inputs and outputs, tach, serial link,
etc., are made to the quick connect type terminal blocks on the left side of the drive. No
lugs are required for these connections. Use #22 AWG to #14 AWG wire. Strip
insulation 0.27" from the end of the wire.
For control power transformer configuration, see paragraph 6.7.4.