Control Block Description
ADDvantage-32 PLUS
4-86
Inputs (Cont.)
UP: Bit
RES: Bit
RET: Bit
2. Outputs
BIOUT: Analog
UNOUT: Analog
3. Implementation
[(TACH1/TACH2) × GAIN] = BIOUT if it is within MIN and MAX, else BIOUT will
equal the limit value. BIOUT is rate limited by the RT value. RT is entered in
units/second and should be set at maximum rate of change at core at max speed.
If the HOLD bit goes high, then BIOUT and UNOUT will be held at their current values.
Releasing this bit lets the block resume calculations.
If UP bit is high, then UNOUT equals the highest BIOUT since the last reset. If the UP
bit is low, then the UNOUT equals the lowest BIOUT since the last reset.
The RES bit is used to reset both BIOUT and UNOUT to the IDIAM value. It stays at
this value as long as the RES bit is high. The RES bit has a higher priority than the
HOLD bit.
Non-retentive Block
On powerup of the ADDvantage-32 PLUS, UNOUT = IDIAM
BIOUT = IDIAM
Retentive Block
On powerup of the ADDvantage-32 PLUS, BIOUT and UNOUT will be initialized under
the following conditions:
If RET = 0, then UNOUT = IDIAM and
BIOUT = IDIAM
If RET = 1, UNOUT and BIOUT are set to their last value. UNOUT and BIOUT
must also be configured to retentive points to be updated automatically on
powerup.