Safety Summary
ADDvantage-32 PLUS AC to DC Power Converter
v
4. When performing hands-on inspections and maintenance, be sure the incoming AC feed
is turned off and locked out. The ADD-32 PLUS and motor may have hazardous
voltages present even if the AC feed is turned off. **NOTE** THE ARMATURE
CONTACTOR DOES NOT REMOVE HAZARDOUS VOLTAGES WHEN
OPENED.
5. When necessary to take measurements with the power turned on, do not touch any
electrical connection points. Remove all jewelry from wrists and fingers. Make sure test
equipment is in safe operating condition.
6. While servicing with the power on, stand on approved insulating material and be sure not
to be grounded.
7. Follow the instructions in this manual carefully and observe all danger notices.
******************************************************
W A R N I N G
ACCURACY OF CUSTOMER-INSTALLED CALIBRATION
AND CONFIGURATION DATA IS IMPERATIVE IN THE
OPERATION OF THIS EQUIPMENT. INCORRECT DATA
MAY CAUSE DAMAGE TO THE ADD-32 PLUS, MOTOR,
AND PROCESS EQUIPMENT.
******************************************************
8. The National Electric Code requires that the end-use customer field mark all electrical
control panels and distribution equipment with an accurate: Arc Flash Hazard Boundary,
an Arc Flash Hazard Category, and the level of the required Personal Protective
Equipment (PPE).
The marking shall be per the requirements of the most current version of NFPA 70
(National Electric Code). The specific marking requirements can be found in the most
current version of NFPA 70 E (Standard for Electrical Safety Requirement for the
Employee Work Place).