Core Software Operation
ADDvantage-32 PLUS ● AC to DC Power Converter
3-26
ADDvantage-32 PLUS faults out and a message is stored in the FAULT FIFO. The
ADDvantage-32 PLUS must be reset before operating again.
For example, two of the most common user faults are overspeed and tach loss conditions.
To set up the ADDvantage-32 PLUS to fault on these two conditions, perform the
following:
1. Find D***:OVER SPEED and D***:TACH LOSS, the two parameters in the
digital data table that represent overspeed and tach loss.
2. Configure D***:OVER SPEED to Y***:USR FAULT 1. Configure
D***:TACH LOSS to Y***:USR FAULT 2.
When either one of these conditions occurs, the ADDvantage-32 PLUS faults out.
3.14 MOTOR PARAMETERS
X*** Parameters Y*** Parameters A*** Parameters
X***:MOTOR IARM Y***:FIELD CNTRL A***:FIL ARM CUR
X***:MOTOR IFLD A***:ARM CURRNT
X***:MFLD % SCALE A***:ARM CURRENT
X***:MFLD ASCALE A***:FLD CURRENT
X***:FLD RESIST A***:FLD CURRNT
A***:MOTOR CEMF
Motor parameters are used to determine the amount of armature and field current being
supplied to the motor. The ADDvantage-32 PLUS current is scaled to the motor current
using the following equations:
100
32
:*** ×=
CurrentPLUSADDvantageRated
CurrentArmatureMotorRated
IARMMOTORX
100
32
:*** ×=
CurrentPLUSADDvantageRated
CurrentFieldMotorRated
IFLDMOTORX
Y***:FIELD CNTRL - Enables the field bridge. If an external field supply is
used, disable this function.