Core Software Operation
ADDvantage-32 PLUS AC to DC Power Converter
3-42
15) If no current is indicated on the microprocessor board, then check to insure that
the PHASE A CT is connected to the PHASE A input on the FIRING MODULE,
PHASE B CT is connected to the PHASE B input, and PHASE C CT is connected
to the PHASE C input. Also check that the cables between the SCR Firing
Adapter and the Field Supply Assembly are in place and secured by tightening
screws on cable ends.
16) If the voltage observed on the scope is negative, instead of the positive pulses
shown in Figure 3-6, reverse all CT polarities. If the CT leads are difficult to
reach, switch the wires for all CTs at J1 of the SCR Firing Adapter.
17) If the voltage waveform observed on the scope has some positive segments and
some negative segments as shown in Figure 3-7, then follow either the 3-CT or
the 2-CT feedback phasing method, using the type your application has been
configured with.
DCAFMC7LAN
Micro Board Iarm Tp
(One CT incorrectly Phased)
-1.5
-1
-0.5
0
0.5
1
1.5
0 2.77 5.545 8.32 11.095 13.87 16.667
Time (ms)
Voltage
Figure 3-7. Micro Board Iarm TP
(One CT Incorrectly Phased)
3-CT Feedback Phasing Method:
18) The 3-CT feedback configuration wiring diagram and jumper settings for the
A20651 SCR Firing Adapter are shown in Figure 3-8. Check the polarity of the
feedback pulses across each burden resistor with the polarities indicated for each
resistor in Figure 3-8. Example: Positive pulses (Figure 3-4) should be observed
for a burden resistor when the scope probe is connected to the resistor + and scope
ground to the resistor -. Confirm these pulses at J1 of the SCR Firing Adapter.
The burden resistor polarities are most easily identified here.