Core Software Operation
ADDvantage-32 PLUS AC to DC Power Converter
3-37
The SCR Firing Adapter Module provides an interface to the existing power bridge.
Refer to paragraph 3.19.3, AFM CURRENT TRANSFORMER PHASING
PROCEDURE, for proper installation and setup. After completing the procedure,
continue with Core Software Operation as you would for a standard ADDvantage-32
PLUS Power Converter.
******************************************************
W A R N I N G
Setting these parameters incorrectly can result in loss of life as
well as damage to equipment. Only qualified personnel should
attempt any changes with these values.
******************************************************
3.19.2 Example Parameter Settings
For example, an AFM module is going to be installed with an existing 540 ADC rated
bridge. The bridge has CT's with one turn on the primary and 4,000 turns on the
secondary. A burden resistor across the CT is rated at 5 OHMS, 5 WATTS.
FOR THESE CONDITIONS, the parameters are set as follows:
BRIDGE RATING
X***:BRIDGE SIZE=540 ADC
X***:ARM CT OUT
sistorReBurden*TurnsimaryPrCT
TurnsSecondaryCT
OUTCTARM:***X =
=
Ohms5*Turn1
Turns4000
= 800