Maintenance and Troubleshooting
ADDvantage-32 PLUS ● AC to DC Power Converter
7-38
d. Connect the new fuse to the adjacent bus bars using the 1/2-13
screw and 1/2" Belleville springs. Tighten to 335-365 in-lb. Be
certain to orient the bus bars properly to each other now, before
attaching to the base.
e. Reattach the fuse to the base using the two 1/2-13 screws and
5/16" Belleville springs. Tighten to 120-140 in-lb.
f. Reattach the vertical bus bar removed in step a.
6. To replace any of the six SCRs CR1-6, perform the following steps in
order:
a. Remove the twisted pairs of wires from the gate leads of the
thyristor to be replaced.
NOTE
Each pair of wires is labeled with a single letter corresponding to a
letter silkscreened on the base.
b. Remove whatever bus bars are required to gain access to the
desired SCR.
c. Using a 5/32" Allen wrench, remove the mounting screws on each
corner of the thyristor and remove the thyristor.
d. Apply a layer of thermally conductive compound to bottom of new
thyristor and reinstall. Tighten the #10-24 socket head screws to
38-50 in-lb. Recheck torque after a minimum of 3 hours and apply
torque seal.
e. Replace the bus bars on the thyristor, using the metric hardware
provided with the semiconductor module. Tighten the terminal
screws to 70-90 in-lb.
f. Reattach the leads removed in step a, being certain to match the
letter designations.
7. The field thyristor (CR7) and field diode (CR8) are on the same panel as
CR1-6, near the bottom. They may be replaced by the following steps:
a. Remove the four terminal screws in the thyristor and diode that
old the two bus bars in place, allowing the bus bars to be lifted.
Comentarios a estos manuales